Adequate Face Velocity for Laboratory Hoods

Multiple organizations have adopted laboratory hood safety standards to determine the effectiveness of a hood in limiting occupational exposure.  One such measure of determining the effectiveness of the hood is by measuring the speed of air entering the hood (i.e. the face velocity).  While face velocity is not the only test method for determining if a hood has the ability to adequately contain the contaminants (see ANSI/ASHRAE 110-1995 Method of Testing Performance of Laboratory Fume Hoods), it is the only performance standard cited by the following organizations.

  • OSHA – General air flow should not be turbulent and should be relatively uniform throughout the laboratory, with no high velocity or static areas (194, 195); airflow into and within the hood should not be excessively turbulent (200); hood face velocity should be adequate (typically 60-100 lfm)
  • NIOSH – The current consensus of the literature is that the average face velocity for a laboratory chemical hood should be in the range of 80–120 ft/min
  • Cal OSHA – The exhaust system shall provide an average face velocity of at least 100 feet per minute with a minimum of 70 fpm at any point, except where more stringent special requirements are prescribed
  • ANSI/AIHA Z9.5-2003 – Design face velocities for laboratory chemical hoods in the range of 80-100 fpm (0.41-0.51m/s) will provide adequate face velocity for a majority of chemical hoods. Hoods with excellent containment characteristics may operate adequately below 80 fpm (0.41 m/s) while others may require higher face velocities. (more…)

Ask the Expert: Ventilation and Fan Requirements

Ask the ExpertD. Jeff Burton, PE, CIH, noted author and OH&S contributor, lends a hand on this “Ask the Expert” question.

Q: How do I go about taking measurements for an old, underperforming laboratory fan for specification of a new fan?

A: When specifying a fan, the two basic numbers you need are Q and SP — called the “System Operating Point,” SOP.

There are two ways of determining “SP.” According to AMCA , one is the Fan Total Pressure (FTP) and the other is Fan Static Pressure (FSP).

FTP represents all energy requirements for moving air through the ventilation system. FTP is calculated by adding the absolute values of the average total pressures found at the fan. If the normal sign convention is followed, then a formula for FTP is:

FTP = TPoutlet – TPinlet

substituting for TP gives

FTP = SPout + VPout – SPin – VPin

If VPout equals VPin, i.e., if the average inlet and outlet velocities are equal, then the VP terms in the above equation cancel, leaving:

FTP = SPoutlet – SPinlet

The fan static pressure (FSP) is defined as the fan total pressure minus the average velocity pressure out of the fan.

FSP = Fan TP – VPout

(The fan static pressure is not defined as the static pressure out minus the static pressure in.)

Substituting the value of FTP into the FSP equation:

FSP = SPout + VPout – SPin – VPin – VPout

The VP (out) terms cancel, leaving

FSP = SPout – SPin – VPin

FSP represents the system losses, i.e., the amount of static pressure converted to useless heat or noise. (more…)